Description
Features
- Conforms to IS/IEC 60947-2
- Range: 1000A , 3Pole 50Ka
- Ics=100% Icu
- Adjustable overload setting from 0.4 to 1.0 x In
- Adjustable short-circuit setting from 1.5 to 8 x Ir
- Inbuilt instantaneous Protection
- Inbuilt ground fault protection from 20%-50% of In
- Adjustable neutral overload protection from 50% to 150% of Ir
- Switchable thermal memory
- Variable trip class
- Front LED Indication
- Panel mounted display for current metering & trip record
- Manual, Rotary and Motorised versions available
- Wide range of accessories
- Above Image is Only for Reference Purpose,Actule Product Image May Very
-
Rated Operational Current-1000
-
Mechanical Life (No. of operating cycles)-20000
-
No. of Poles-3P
-
Rated Operational voltage (Ue)-415V AC
-
Rated Insulation Voltage Ui (V)-800 V
-
Conformance to Standards-IEC 60947-1, EN 60947-1, IS/IEC 60947-1 IEC 60947-2, EN 60947-2, IS/IEC 60947-2 IEC 60947-3, EN 60947-3, IS/IEC 60947-3 IEC 60947-4, EN 60947-4, IS/IEC 60947-4
-
Rated impulse withstand voltage (Uimp)-8 kV
-
Operational Frequency (Hz)-50/60 Hz
-
Release Type-MTX1.0
-
Rated Short Circuit Breaking capacity Icu(kA)-DN4N MCCB 1000 3P 415V AC 50kA MTX1.0 50/60 Hz
-
Rated Sevice circuit breaking capacity (Ics as % of Icu) @415VAC-50kA
-
Ambient temperature–5°C to 55°C
-
Suitable for isolation-Yes
-
Load-line bias-No
-
Electrical Life (Operating Cycles)-3000
-
IP Protection-IP40
-
Pollution Degree-III
-
Width(mm)-210
-
Height(mm)-370
-
Depth(mm)-143
Note: L&T Switchgear Business is now Lauritz Knudsen Electrical & Automation.
Some products may still be labelled as L&T Switchgear Business until existing stock lasts. The quality and service you trust remain unchanged.